product features
three remote functions: telemetry (including direct flow), remote signaling, and remote control;
protection functions: three-phase three-section overcurrent protection function, zero sequence protection function, reclosing and blocking reclosing function;
intelligent distributed logic function: achieving local fault clearing, automatic fault isolation, automatic transfer of power supply, and automatic restoration of power supply in non faulty sections; logic manual, automatic reset and other functions;
remote/local operation: the remote/local closing and opening operations are mutually locked, and the control outlet is controlled by the soft and hard pressing plates for on/off;
power function: dual power switching, automatic seamless switching to backup power supply in case of ac power loss, and automatic management (battery activation, alarm, protection) function for backup power supply;
communication function: multiple network and serial ports, supporting multiple communication protocols; wireless communication: capable of wireless communication through touch laptops;
wireless communication: capable of wireless communication through touch laptops;
status indication: there are obvious local status indication signals for operation, communication, line faults, etc;
data processing function: arbitrary configuration and combination of data sent by the main station; distribution transformer load rate, three-phase imbalance, remote sensing exceeding limit, extreme value, qualification rate statistics, etc;
fault detection: achieving on-site fault clearing, automatic fault isolation, automatic transfer of power supply, and automatic restoration of power supply in non fault sections; logic manual, automatic reset and other functions;
technical parameter
telemetry
|
rated voltage
|
ac220v/100v, accuracy ≤ 0.5%
|
rated current
|
5a/1a, accuracy ≤ 0.5%
|
power (active, reactive, power factor)
|
≤ 1%
|
dc voltage
|
accuracy ≤ 0.2%
|
remote signaling
|
remote signaling power supply
|
dc24v/dc48v adaptive
|
soe resolution
|
≤ 2ms
|
software anti shake time
|
0-65535ms can be set
|
single/dual point remote signaling optional
|
|
remote control
|
output method
|
empty contact output, pulse duration 1-65535ms can be set
|
contact rating
|
ac 250v/5a, dc 80v/2a, or dc 110/0.5a pure resistive load
|
contact life
|
on/off ≥ 105 times
|
telemetry
|
ua, ub, uc, u0 (or uab, ubc), ia, ib, ic, i0 (or synthetic), 1 dc quantity
|